Basic PDU - 3.6kW, CB-26V0AE01F6

Key Features

  • Branch circuit protection
    Branch Circuit Protection
    This PDU meets the UL and IEC 60950-1 requirement for branch circuit protection through use of UL489 rated magnetic-hydraulic circuit breakers or UL248 fuses.
  • High retention outlets
    High Retention Locking Outlets
    Receptacles have high retention and are compatible with P-Lock type power cords.
  • Flexible mounting
    Flexible Mounting
    Includes standard button mounts along with provisions for custom mounting brackets (contact Server Technology for details).

Description

The Server Technology® Basic PDU provides reliable power distribution for installing IT equipment into the rack/cabinet.

Inputs

Input Voltage (V): 208
Input Plug: IEC C20 100-240V Inlet
Input Current (A): 20
Input Current Rated (A): 16
Input Power Capacity (kW): 3.6
Requires PTCORD-L1, -L2, -L3, -L4, -L5, -L6, or –L7

Outputs

Connector Rating
(24) x IEC 60320/C13 North American Rating: ≤ 12A @208V L-N (15A Peak)
Global Rating: ≤ 10A @230V L-N
(2) x IEC 60320/C19 North American Rating: ≤ 16A @208V L-N (20A Peak)
Global Rating: ≤ 16A @230V L-N

Branch Circuit Protection

UL489 Compliant 2-pole, 20A trip circuit breakers, two (2) branch, rating: ≤ 16A, 5 kAIC Interrupt Rating

Physical

Dimensions: 35.5in tall x 1.75in wide x 1.75in deep [902mm x 45mm x 45mm]

Environmental

Operating Environment: 32°F to 122°F / 0°C to 50°C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevation
Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation
Quiescent / Unloaded Power Draw: < 10W for all configurations

Communications & Security

Not Applicable

Certifications

North American:
Safety (TUVR certified, cTUVus mark)
  • UL Std. 60950-1, 62368-1
  • CAN/CSA-C22.2 No. 60950-1, CAN/CSA-C22.2 No. 62368-1


Global:
Safety
  • EN 62368-1 (TUVR certified, T-mark)
  • IEC 60950-1 incl. regional, national and harmonized differences (IECEE CB scheme)
  • IEC 62368-1 incl. regional, national and harmonized differences (IECEE CB scheme)

  • RoHS, European Hazardous Materials Directive, 2011/65/EU
  • WEEE Compliant
  • CE Mark
  • UK Legislation
  • RoHS, Electrical Equipment (Safety)

Measurement Accuracy

Input Measurement Accuracy:
LED Current = ± 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolution
GUI Current = ± 5% at 0.01 amp resolution (above 0.25 amp)

More Info:

Download Datasheet Contact Us